Characterizing Job Power Elasticity for Power-Flexible AI Training

Authors: Philip ColangeloCharles DawsonShayan SenguptaAyse CoskunVarun Sivaram

Abstract

Large language model (LLM) training is among the fastest-growing sources of electricity demand in modern data centers, and power availability is a primary bottleneck to continued AI infrastructure growth. Making the power consumption of these workloads flexible could unlock additional power for AI growth, limit increases in electricity prices, and improve the utilization of existing grid infrastructure. However, to realize this flexibility, we must first understand how the performance of training workloads changes when GPU power is reduced. This paper presents the first systematic characterization of \emph{job power elasticity} (the sensitivity of throughput to power reductions) in LLM training. To quantify elasticity, we introduce the \emph{Power Flexibility Index (PFI)}, a normalized metric that quantifies the performance cost of power reductions and provides a control primitive for SLA-aware power flexibility. We collect data from 131 LLM training runs on H200 (plus 24 H200 validation runs and 34 matched H100 runs), including both dense and mixture-of-experts models, pretraining and fine-tuning tasks, and up to 32 GPUs. We find that LLM training jobs exhibit substantial but variable power elasticity, and we identify telemetry signals that predict PFI at runtime. Finally, we demonstrate that PFI-aware power allocation maximizes total tokens/second throughput under power constraints. Under a 30% power reduction, PFI-aware power allocation recovers ~1.5k tokens/s per job, 63% of the performance gap between an equal-weight allocation and an oracle with perfect information. Our results establish power elasticity as a measurable property of training jobs and provide a foundation for power-aware, grid-responsive AI infrastructure.

Explore similar work

May 20, 2026cs.AI

PALS: Power-Aware LLM Serving for Mixture-of-Experts Models

Large language model (LLM) inference has become a dominant workload in modern data centers, driving significant GPU utilization and energy consumption. While prior systems optimize throughput and latency by batching, scheduling, and parallelism, they largely treat GPU power as a static constraint rather than a controllable resource. In this paper, we present a power-aware runtime for LLM serving, PALS, that treats GPU power caps as a first-class control knob and jointly optimizes them with software parameters such as batch size. The system combines lightweight offline power-performance models with a feedback-driven controller to select configurations that satisfy throughput targets while maximizing energy efficiency. We implement PALS within an existing LLM serving framework, vLLM, demonstrating that it requires no model retraining or API changes. Across multi-GPU systems and both dense and mixture-of-experts (MoE) models, PALS improves energy efficiency by up to 26.3%, reduces QoS violations by 4x to 7x under power constraints, and tracks dynamic power budgets. These results highlight the potential of integrating power control directly into LLM inference runtimes, enabling energy-proportional and grid-interactive AI systems.
Can Hankendi, Rana Shahout, Minlan Yu +1
Jul 27, 2026cs.AI

Cutting AI Datacenter Energy with Reinforcement Learning: Measured Power Control of LLM Training from One GPU to the Fleet

Reinforcement-learning post-training dominates modern language-model development, yet its power behavior on GPU hardware has not been characterized, and datacenters manage GPU power with workload-blind mechanisms, static caps and reactive throttling, that slow hardware indiscriminately. We instrument GRPO training with half-second power telemetry at 7B, 14B, and 72B scales on one to four A100s (380,000+ samples), and train a PPO meta-controller that adapts the workload's own generation parameters to measured power. Against the full 500-step 7B trace, the controller cuts power-limit violations by 89.8% while increasing token output by 18.1% and energy efficiency by 26.2% (tokens per MWh). Deployed live at 72B, the same controller family yields replicated null results, diagnosed as the group-size actuator losing authority under model sharding. An actuator-authority sweep shows the same parameters applied as generation concurrency retain 17-22% power authority, isolating an occupancy-versus-volume principle; a controller rebuilt on that actuator controls a live 72B rollout-generation workload across three replications: 35.7% more output than a static safe baseline at 2.27 +/- 1.08% budget violations, 87.2% fewer violations than uncontrolled operation, and the best mean throughput and energy per token among constrained controllers, with an adaptive threshold rule matching it in one of three operating conditions. Under realistic measurement windows the original 72B transients fall from 23.6% at half-second resolution to 1.6% at 30 s and zero at 5 min; a composed 16-GPU fleet shows zero violations at 30 s and longer, with peak demand at 50-56% of nameplate. For this fleet mix, roughly twofold oversubscription of nameplate appears feasible, subject to operator validation. We quantify the economic and carbon consequences and specify a low-cost operator pilot.
Eliseo Curcio
Jul 2, 2026cs.DC

WattGPU: Predicting Inference Power and Latency on Unseen GPUs and LLMs

Large Language Model (LLM) inference workloads are a rapidly growing contributor to data center energy consumption. Optimizing these deployments requires matching specific LLMs to the most efficient GPUs, but operators currently lack the tools to do so without exhaustively profiling each combination. While some predictive models exist, they still require profiling data and struggle to generalize to hardware unseen during training. To address this, we introduce \textit{WattGPU}, featuring two predictive models for mean GPU power draw and Inter-Token Latency (ITL). Our approach leverages only publicly available LLM metadata and GPU specifications, eliminating the need for hardware access or profiling while enabling generalization to unseen NVIDIA server-grade GPUs and LLMs. We evaluate our models using rigorous leave-one-GPU-out and leave-one-LLM-out cross-validation on a dataset of 42 open-source LLMs (0.1B--27B parameters) and 8 GPUs under both offline and server scenarios. The mean power draw model achieves a median absolute percentage error of 3.4%\leq3.4\% for offline and 13.5%\leq13.5\% for server scenarios on unseen GPUs, while the latency model achieves 8.5%\leq8.5\% in server mode, both maintaining strong GPU ranking correlations for server scenarios (Kendall τ0.76τ\geq0.76). Compared to standard physically grounded baselines -- Load-Scaled Thermal Design Power (TDP) for power draw and roofline for latency -- our models reduce median absolute percentage error by approximately 4×\times on unseen LLM-GPU combinations for server scenarios or approximately 2×\times for completely unseen GPUs. WattGPU's data and code are publicly available at https://github.com/maufadel/wattgpu.
Mauricio Fadel Argerich, Jonathan Fürst, Marta Patiño-Martínez