In a Houston 2024 replay, replacing a fixed 20 percent battery reserve with a county-risk threshold raises observed five-hour backup coverage from 75.0 percent to 86.5 percent and adds USD 10.2 in modeled annualized margin per home (paired 95 percent interval: USD +1.7 to USD +21.7). The paired coverage-gain interval includes zero. This is a conditional simulation result, not measured company reliability. Residential batteries face this tradeoff because market discharge consumes energy also needed for household outages. We release HomeFleet-ERCOT, combining observed prices and county outages with identified simulated homes and causal controller inputs. We compare independent-home optimization with 21 proximal policy optimization (PPO) training runs; ten promise-cost candidates span 31.1 percent-96.3 percent backup coverage. Of these, 10 have lower modeled margin than fixed 20 percent, and 3 also have lower coverage. Chronological, geographic, fleet, and storm tests examine transfer. An alert charging override has a conditional energy-and-power sufficiency guarantee, but only 19.5 percent of 41 county mass-outage episodes provide enough continuous warning for every battery preset. Synthetic tests include short, missed, and false warnings, load uplift, capacity loss, and dropout. A static AC audit retains existing feeder violations; aging comparisons expose model sensitivity. The released benchmark, controllers, and checkpoints provide a reproducible basis for comparing these tradeoffs. This work supports the design of residential battery programs that assess market value and household backup service together.
Figures & tables
Figure 1: Historical price/outage context, 2021–2025. Each point is one local day. Dashed lines mark the two descriptive thresholds; both axes use logarithmic scales. The prices span Houston, North, South, Austin Energy, and CPS load zones. Statewide outage totals are not the household replay’s reliability metric.
Figure 2: Houston 2024: economics versus simulated backup service. Higher values on either axis are preferable. Margin is paired against fixed 20% and adjusted for terminal inventory. Crosses show every promise-cost PPO candidate; the selected candidate and its alert override are marked separately. Error bars for fixed 20%, threshold 0.1, and guarded PPO show 95% window-bootstrap intervals. Lines connect settings within a family and do not imply a fitted Pareto frontier.
Controller
Δ margin [95% CI]
Promise [95% CI]
Unserved
Fixed 20%
+0.0 [0.0, 0.0]
75.0 [66.7, 96.3]
204.0
Fixed 50%
-79.5 [-138.5, -34.1]
94.0 [92.0, 100.0]
189.1
Hold near 90%
-104.3 [-145.1, -72.6]
95.8 [93.5, 100.0]
177.8
Storm rule
-10.2 [-17.6, -3.7]
85.9 [83.3, 97.9]
190.1
Historical tiers
-73.6 [-126.4, -32.4]
91.9 [90.3, 100.0]
189.9
Risk DP 5
-25.4 [-37.7, -15.2]
93.3 [87.0, 100.0]
191.8
Table 1: Houston 2024, 100 simulated homes. Margin difference is USD/home-year and unserved energy is kWh/home-year; promise is a percentage. Brackets are 95% bootstrap intervals. Higher margin/promise and lower unserved energy are preferable. All regular windows, including the final partial window, receive duration-appropriate weight. Named event evaluations are excluded from these aggregates.
Figure 3: Transfer of the fixed validation choices. The upper panel shows annualized margin differences from the local fixed-20% reference; positive is preferable. The lower panel shows episode-pooled five-hour promise; higher is preferable. The 2026 replay is partial-year and has no observed outage truth. Metro comparisons use the same tariff and hardware assumptions with different public building pools and county traces.
Figure 4: Controlled joint-event stress: $5,000/MWh price, eight-hour outage, 10% initial SOC, 25 kWh batteries, 2 kW demand, no PV/dropout, and full state of health. Warning lead varies while other inputs remain fixed. Promise rate is higher-is-better; onset SOC explains the available backup energy. The wider synthetic suite includes 86 indexed cases, including false/missed alerts, load uplift, reduced state of health, and dropout.
Appendix figures & tables14 assets
Supplementary material from the paper’s appendix.
Appendix
Symbol
Meaning and units
i,c,z,t
Home, county, load zone, dispatch interval
Δ
Dispatch duration, 0.25 h
Li,t,Vi,t
Household demand and PV output, kW
Eˉi,Ei
Rated and SOH-adjusted available capacity, kWh
ei,t,eimin
Stored energy and physical minimum, kWh
Ri,t
Connected operating reserve target, kWh
Appendix
Table 2: Notation used in the model and results. Stored-energy requirements account for discharge efficiency; delivered unserved energy is scored in kWh at the household.
Run
Δ margin
Promise (%)
Mean SOC (%)
Throughput
pc_lam20_s1
-93.4
96.3
98.7
1,106.4
pc_lam20_s2
-105.6
86.3
96.2
2,090.4
pc_lam20_s3
-81.3
89.8
89.7
2,797.2
pc_lam20_s4
-159.3
91.9
56.5
12,048.3
pc_lam20_s5
-200.0
31.1
10.9
1,084.3
pc_lam5_s1
-55.3
96.3
97.4
2,323.0
Appendix
Table 3: All ten promise-cost candidates on Houston 2024. Asterisk denotes the fixed validation selection. Margin difference is $/home-year against fixed 20%; throughput is charge plus discharge kWh/home-year. Promise and mean SOC are percentages. Names encode penalty and seed.
Run
Δ margin
Promise (%)
Mean SOC (%)
Throughput
fixed_lam5_s0
-100.3
94.7
65.4
2,502.2
fixed_lam5_s1
-86.3
96.3
97.0
754.6
learned_lam1_s0
-46.9
95.6
88.9
1,207.5
learned_lam1_s1
-89.9
90.2
92.6
4,377.0
learned_lam20_s0
-2.2
80.3
95.1
3,225.7
learned_lam20_s1
-83.8
96.3
98.4
1,298.9
Appendix
Table 4: All eleven full-outage-cost and reserve-ablation runs, with the same units as Table 3 . “None” removes the operating reserve but retains physical battery limits. These runs do not participate in selecting the headline promise-cost candidate.
Controller
Cash/yr
Adjusted/yr
Daily CVaR 5
Worst 7 blocks
Fixed 20%
493.0
475.3
-0.47
1.30
Fixed 50%
405.9
395.8
-0.48
1.19
Hold near 90%
373.9
371.0
-0.79
0.56
Storm rule
482.0
465.2
-0.91
0.83
Historical tiers
414.5
401.7
-0.48
1.22
Risk DP 5
467.7
449.9
-0.55
1.11
Appendix
Table 5: Houston 2024 gross outcomes, in dollars per home. Cash and adjusted margins are annualized; daily CVaR and worst seven-block values use complete 24-hour cash blocks (Appendix B ). Higher values are preferable. Aging charges are excluded.
Controller
Homes with outages
Promise p5 %
Unserved p95 /yr
Fixed 20%
100
33.3
577.4
Fixed 50%
100
66.2
547.2
Hold near 90%
100
66.7
526.6
Storm rule
100
42.7
547.7
Historical tiers
100
49.6
548.4
Risk DP 5
100
59.9
559.2
Appendix
Table 6: Houston 2024 household tails. Promise p5 is the fifth percentile of household episode-success rates among homes with outages (higher is better). Unserved p95 is the 95th percentile of annualized household unserved energy, kWh/home-year (lower is better). These empirical quantiles do not certify household risk budgets.
Season
Dispatch
Hours
Δ margin/wk
Promise%
Episodes
DJF
Fixed 20%
2,400
+0.0
88.9
18
DJF
Threshold 0.1
2,400
+0.0
88.9
18
DJF
Risk DP 5
2,400
-0.3
100.0
18
DJF
Selected PPO
2,400
-0.7
100.0
18
DJF
PPO + override
2,400
-0.6
100.0
18
MAM
Fixed 20%
2,016
+0.0
83.1
219
Appendix
Table 7: Houston 2024 seasonal window cohorts, assigned by first local timestamp: DJF (Dec–Feb), MAM (Mar–May), JJA (Jun–Aug), and SON (Sep–Nov). Boundary-crossing windows remain whole; these are not exact calendar-season totals. Hours and episodes are observed; margin is standardized $/home-week against fixed 20%. Higher margin/promise is better. The released CSV retains all controllers/datasets and paired window-bootstrap intervals.
Figure 5: Houston storm traces under identical sampled homes and outages. Top: observed price (gray, left axis) and recorded county outage fraction (orange, right axis). Middle: average fleet SOC, which can conceal individual depleted homes. Bottom: cumulative unserved energy per sampled home, lower is preferable. Full-outage unserved energy can continue rising after a five-hour commitment has already succeeded. Time is local.
Window
Controller
Margin/wk
Promise (%)
Unserved
Episodes
HOU: Uri
Fixed 20%
-865.1
90.9
5.7
198
HOU: Uri
Storm rule
-783.8
100.0
2.1
198
HOU: Uri
Risk DP 5
-845.4
94.4
5.3
198
HOU: Uri
Selected PPO
-908.6
69.7
8.1
198
HOU: Uri
PPO + override
-785.4
98.0
3.4
198
HOU: Elliott
Fixed 20%
81.1
100.0
0.0
1
Appendix
Table 8: Named-window results. Margin is terminal-adjusted $/home-week, promise is a percentage, and unserved energy is kWh/home over the actual window. Episode counts refer to simulated household episodes and remain common across controllers. An unavailable promise means no scored episode. Higher margin/promise and lower unserved energy are preferable.
Threshold%
Events
Active%
Past 24 h%
Lead ≥4 h%
1
455
35.8
47.9
2.9
5
41
85.4
97.6
19.5
Appendix
Table 9: County warning coverage, all six evaluated counties, 2019–2025. Threshold is the customers-out percentage defining an audit event. “Active” means at onset; “past 24 h” means any recent qualifying warning and does not require continuity. The last column requires continuous active lead of at least four hours, the worst preset’s charging time from its physical minimum. These fractions are not household service-success probabilities.
Year
Horizon (h)
ROC AUC
Avg. precision
Brier
Positive%
2021
1
0.952
0.744
0.0114
2.50
2021
6
0.842
0.443
0.0307
4.27
2021
24
0.728
0.357
0.0767
9.73
2024
1
0.963
0.815
0.0083
2.49
2024
6
0.876
0.599
0.0225
4.00
2024
24
0.774
0.415
0.0648
8.75
Appendix
Table 10: Out-of-training-period county classifier diagnostics pooled across the twelve weather-covered Texas counties used to fit/evaluate the forecast. Larger ROC AUC/average precision and smaller Brier score are preferable. Positive prevalence differs by year/horizon. Evaluation fleets use six of these counties. Calibration on 2020 does not imply calibration under later distribution changes.
Scenario
Dispatch
Δ margin/wk
Promise%
Episodes
base 100
fixed20
+0.0
85.9
608
base 100
storm
+7.2
89.8
608
base 100
risk5
+3.3
94.9
608
size 500
fixed20
+0.0
84.5
2966
size 500
storm
+11.5
88.7
2966
size 500
risk5
+4.1
94.5
2966
Appendix
Table 11: Six-window fleet sensitivity collection, not annual evaluation. Margin difference is $/home-week against fixed 20% under the same scenario and is weighted by duration. Promise pools household episode/failure counts across the six windows. Scenario names specify fleet size, a 70% Core mix, or 20% independent per-interval dropout; other settings match the base 100-home scenario. All sampled source pools contain 300 profiles.
Homes
Dispatch
Mean ms/interval
SD
100
fixed20
1.80
0.02
100
risk5
2.18
0.11
100
ppo
0.34
0.00
100
ppo guard
0.35
0.02
500
fixed20
8.47
0.09
500
risk5
9.79
0.14
Appendix
Table 12: Mean CPU wall time per interval for complete forecast/decision/simulation loops, excluding episode reset. Three measured one-day repetitions follow a warm-up for each configuration. The CSV records platform, backend, thread count and all repetitions. DP replans hourly with 32 grid points; PPO acts every interval. These are implementation timings, not communication delays or isolated neural-network inference times.
Day
Dispatch
Pen.%
Voltage range
UV%
OV%
Line%
beryl
Load/PV reference
0
[0.812, 1.108]
5.2
9.4
3.1
beryl
Fixed 20%
30
[0.773, 1.108]
14.6
22.9
24.0
beryl
Risk DP 5
30
[0.812, 1.108]
15.6
19.8
25.0
beryl
PPO + override
30
[0.812, 1.108]
12.5
21.9
28.1
beryl
Fixed 20%
100
[0.793, 1.108]
22.9
32.3
28.1
beryl
Risk DP 5
100
[0.813, 1.109]
24.0
35.4
29.2
Appendix
Table 13: Full AC audit. Penetration is the percent of load locations assigned battery dispatch. Voltage range is across phase nodes at graph-reachable buses and all intervals, using the mask above. UV/OV are percentages of intervals with any retained phase voltage below 0.95/above 1.05 pu; Line is the percentage with any line current above its nominal ampacity. A small minimum is retained even when the snapshot solver reports convergence. Eighteen phase nodes at unreachable buses have zero voltage and are counted separately in the released CSV. The reference’s existing violations prevent treating controller changes as a calibrated grid-compliance assessment.
Dispatch
Mean SOC (%)
ET
Rainflow
BLAST
fixed20
56.6
0.54
3.05
4.40
hold90
80.5
0.39
2.13
5.75
storm
58.3
0.55
3.10
4.49
risk5
65.3
0.50
2.51
4.93
ppo
77.8
0.38
2.17
5.40
ppo guard
77.8
0.38
2.18
5.40
Appendix
Table 14: Mean across four 20-home window sensitivities (Beryl, derecho, August heat, and regular window w10). ET and rainflow columns are annualized capacity-loss percentages; BLAST repeats each trace to one year. Equal weighting across these windows is a reporting convention, not a representative annual climate mix. Mean SOC is a percentage. Lower predicted fade is preferable within a model; values across model classes are not interchangeable.
Building Energy Management coordinates HVAC, storage, and flexible loads to reduce energy use and emissions while maintaining comfort and reliable service.
Public charging of electric vehicles (EVs) adds a large and synchronized load to the distribution feeders. In most networks, it is rare to overload a feeder at the same time. When it does happen, the consequences can be severe: an overloaded feeder stresses its transformers and can trigger cascading outages across a city. Planners who design for high reliability therefore need to estimate very small outage probabilities. To that end, plain Monte Carlo estimation with an expensive grid simulator can require a prohibitively large number of runs for this task. To reduce the number of runs, we propose a control variate (CV) built from a learned classifier of the outage, trained on cheap observable features such as temperature and load forecasts. We show that for any binary learner, the variance reduction is an explicit function of its recall and false-positive rate. Furthermore, we show that control variate based on a Gaussian proxy of the load loses its effect as outages become rarer, while a learner with non-vanishing precision keeps removing a fixed fraction of the variance even in the extreme rare-event regime. We verify these results in numerical experiments using a feeder-overload simulator across three orders of magnitude of outage probability and obtain that even weak learner with a single feature can remove a quarter of the variance, while a boosted-tree learner is able to remove about 60%. We then apply the estimator to the feeder network of Surabaya, Indonesia, in which the Gaussian load model leaves every feeder three to seven times the one-day-in-ten-years blackout target. At the same simulation budget, planning the reserve with the learned CV and a 95% confidence limit reduces the city-wide blackout days by a third compared with Monte Carlo. These results show that learned control variates can help planners design distribution grids that stay reliable against rare outages.
Sulyman Iyanda, Mansur Arief
Industrial and Systems Engineering Department, King Fahd University of Petroleum and Minerals, Dhahran, Saudi Arabia
Battery energy storage system (BESS) dispatch must preserve operational feasibility while declining price spreads reduce the margin available to pay for cycling. We study a proximal policy optimization (PPO) controller whose pre-selection physical action mask and emergency projection are separated from a causal, forecast-informed economic advisory. All forecast-dependent methods receive the same causal 24-step forecast and grid-side settlement. Across five PPO seeds, advice-on net profit is 30.59 and 18.04 USD per 336-hour T1 and T2 window, versus 36.77 and 22.94 USD for proxy-cost MPC; PPO remains below this reference in both periods. Advice raises T2 profit from 16.45 to 18.04 USD while reducing throughput, but is immaterial in T1. On disjoint weekly blocks, PPO is stable under daily, weekly, and blended seasonal forecasts, weakens under persistence, and remains below proxy-cost MPC. Paired diagnostics localize changes to the observed 5-10 USD/MWh regime with mixed SoC-dependent effects. An M0-M6 ablation shows that mask removal sends thousands of infeasible requests to projection, while removing both physical layers exposes ramp violations. The evidence separates economic screening from feasibility enforcement without claiming formal safety, lifecycle-optimal aging, or RL dominance.
Kuanlin Chen, Chen-Wei Kuo, Cheng-En Ou
Independent Researcher Taoyuan, Taiwan · National Tsing Hua University Hsinchu, Taiwan · Independent Researcher
Residential battery energy storage systems (BESS) are increasingly deployed alongside photovoltaic (PV) generation to reduce household energy costs under volatile time-of-use (TOU) tariffs. Model predictive control (MPC) is a widely adopted optimisation strategy for home energy management systems (HEMS), typically formulated to minimise net energy cost, subject to physical and operational constraints. However, battery degradation is rarely embedded in the optimisation objective, meaning its cost is unquantified and aggressive; high-cycle-count strategies could incur significant losses once deployed to physical systems. This paper presents a receding-horizon mixed-integer linear programming (MILP) baseline for a UK residential HEMS, using demand data from the REFIT dataset. A 3 by 3 sensitivity study is conducted across three battery sizes and three PV array sizes, with post-hoc degradation cost estimated using the Naumann stress model and rainflow cycle counting. Results show that degradation remains constant for each battery size and can exceed energy cost savings by up to 1,060 %. These results demonstrate that energy-cost-only optimisation systematically underestimates the true system cost, motivating a degradation-aware control formulation.
Dawood Butt, Nandor Verba
WMG, The University of Warwick, Coventry, United Kingdom