Extreme weather events and cyberattacks can cause component failures and disrupt the operation of power distribution networks (DNs), during which reconfiguration and load shedding are often adopted for resilience enhancement. This study introduces a topology-aware graph reinforcement learning (RL) framework for outage management that embeds higher-order topological features of the DN into a graph-based RL model, enabling reconfiguration and load shedding to maximize energy supply while maintaining operational stability. Results on the modified IEEE 123-bus feeder across 300 diverse outage scenarios demonstrate that incorporating the topological data analysis (TDA) tool, persistence homology (PH), yields 9-18% higher cumulative rewards, up to 6% increase in power delivery, and 6-8% fewer voltage violations compared to a baseline graph-RL model. These findings highlight the potential of integrating RL with TDA to enable self-healing in DNs, facilitating fast, adaptive, and automated restoration.
Figures & tables
Fig. 1 : Architecture of the policy network (PH-GCAPCN).
Fig. 2 : Training performance for the proposed RL model based on PH-GCAPCN and the baseline RL model using GCAPCN.
Metric
Test Set 1
Test Set 2
Test Set 3
PH-GCAPCN
GCAPCN
PH-GCAPCN
GCAPCN
PH-GCAPCN
GCAPCN
Reward ( R )
0.4626 ± 0.5757
0.3923 ± 0.5692
0.5132 ± 0.5540
0.4710 ± 0.5407
0.5538 ± 0.4842
0.5010 ± 0.4659
Energy Supplied ( Esupp )
0.6760 ± 0.3433
0.6374 ± 0.3265
0.7119 ± 0.3234
0.6821 ± 0.3129
0.7302 ± 0.2913
0.6921 ± 0.2769
Voltage Violation ( Vviol )
0.2134 ± 0.2330
0.2282 ± 0.2276
0.1932 ± 0.2189
0.2057 ± 0.2166
0.1763 ± 0.1942
0.1911 ± 0.1909
TABLE I : Performance of PH-GCAPCN and GCAPCN RL models across three test samples. Values are reported as mean ± std over 100 distinct out-of-sample scenarios.
Test Set
Reward
Energy Supplied
Voltage Violation
1
6.83×10−4∗∗∗
1.26×10−8∗∗∗
9.42×10−4∗∗∗
2
3.82×10−5∗∗∗
3.75×10−9∗∗∗
2.73×10−5∗∗∗
3
2.15×10−7∗∗∗
7.39×10−8∗∗∗
9.04×10−5∗∗∗
TABLE II : Paired t-test p -values comparing PH-GCAPCN and GCAPCN over 100 matched outage scenarios per test sample.
Fig. 3 : Test performance comparison of PH-GCAPCN and GCAPCN models
Department of Electrical Sustainable Energy, Delft University of Technology, Mekelweg 4, Delft, 2628 CD, The Netherlands · Beijing Energy Quant Ltd., Haidian, Beijing, 53100, China