Gated Graph Attention Networks for Predicting Duration of Large Scale Power Outages Induced by Natural Disasters
Authors: Chenghao Duan, Chuanyi Ji, Anwar Walid, Scott Ganz
Organizations: School of Electrical and Computer Engineering, Georgia Institute of Technology, Atlanta, GA, USA · Department of Electrical Engineering, Columbia University, New York, NY, USA · School of Business, University of California, Riverside, Riverside, CA, USA
The occurrence of large-scale power outages induced by natural disasters has been on the rise in a changing climate. Such power outages often last extended durations, causing substantial financial losses and socioeconomic impacts to customers. Accurate estimation of outage duration is thus critical for enhancing the resilience of energy infrastructure under severe weather. We formulate such a task as a machine learning (ML) problem with focus on unique real-world challenges: high-order spatial dependency in the data, a moderate number of large-scale outage events, heterogeneous types of such events, and different impacts in a region within each event. To address these challenges, we develop a Bimodal Gated Graph Attention Network (BiGGAT), a graph-based neural network model, that integrates a Graph Attention Network (GAT) with a Gated Recurrent Unit (GRU) to capture the complex spatial characteristics. We evaluate the approach in a setting of inductive learning, using large-scale power outage data from six major hurricanes in the Southeastern United States. Experimental results demonstrate that BiGGAT achieves a superior performance compared to benchmark models.
Figures & tables
Fig. 1: Spatial heterogeneity and dependency of power outages from six hurricanes: (a) Florence, (b) Irma, (c) Laura, (d) Michael, (e) Sally, (f) Zeta. Dark lines: wind boundaries (64, 50, and 34 knots). Clusters on regions with different impacts: Red - significantly impacted counties; Yellow - less impacted counties. Clustered by wind and outage duration.
Events
Short
Medium
Long
Florence
68
21
9
Irma
158
127
29
Laura
76
18
17
Michael
127
31
18
Sally
62
7
1
Zeta
179
44
12
TABLE I: Data summary: number of counties for three classes of outage durations
Fig. 2: Overall BiGGAT structure: Node features are fed into the Bimodal Embedding, then passed through the Gated Graph Attention mechanism. The aggregated messages are transformed to outputs by a Linear Readout layer.
Events
Highest n
Global n-hop Moran’s I
Florence
3
0.273∗(6.806)
Irma
6
0.070∗(4.723)
Laura
5
0.112∗(3.499)
Michael
3
0.053∗(1.998)
Sally
2
0.110∗(1.864)
Zeta
4
0.154∗(6.049)
TABLE II: Global n-hop Moran’s I of peak outage number
Fig. 3: Model performance comparison for (a) Florence, (b) Irma, (c) Laura, (d) Michael, (e) Sally, and (f) Zeta. Each subplot shows classification accuracy, Macro F1, and balanced accuracy for XGB, RF, GAT, BiGAT, and BiGGAT.
Extreme weather events, such as severe storms, hurricanes, snowstorms, and ice storms, which are exacerbated by climate change, frequently cause widespread power outages. These outages halt industrial operations, impact communities, damage critical infrastructure, profoundly disrupt economies, and have far-reaching effects across various sectors. To mitigate these effects, the University of Connecticut and Eversource Energy Center have developed an outage prediction modeling (OPM) system to provide pre-emptive forecasts for electric distribution networks before such weather events occur. However, existing predictive models in the system do not incorporate the spatial effect of extreme weather events. To this end, we develop Spatially Aware Hybrid Graph Neural Networks (SA-HGNN) with contrastive learning to enhance the OPM predictions for extreme weather-induced power outages. Specifically, we first encode spatial relationships of both static features (e.g., land cover, infrastructure) and event-specific dynamic features (e.g., wind speed, precipitation) via Spatially Aware Hybrid Graph Neural Networks (SA-HGNN). Next, we leverage contrastive learning to handle the imbalance problem associated with different types of extreme weather events and generate location-specific embeddings by minimizing intra-event distances between similar locations while maximizing inter-event distances across all locations. Thorough empirical studies in four utility service territories, i.e., Connecticut, Western Massachusetts, Eastern Massachusetts, and New Hampshire, demonstrate that SA-HGNN can achieve state-of-the-art performance for power outage prediction.
Xuyang Shen, Zijie Pan, Diego Cerrai +4
University of Connecticut · Western Connecticut State University · Eversource Energy
Identifying vulnerable transmission lines in power grids before a cascading failure occurs is challenging: existing methods can learn inter-line failure correlations from cascade data, but they are trained and evaluated on a single grid, and transferring the learned knowledge to an unseen grid remains an open problem. We address this by training a single Gated Recurrent Unit (GRU)-gated Graph Attention Network on combined cascading failure data from limited training grids and applying it directly to any unseen grid without retraining. A GRU gate controls what information each node retains or discards at each cascade iteration. Empirical evaluation shows that the model transfers zero-shot to multiple new grids spanning inter-time and inter-domain settings. Using information extracted from the trained model, we consistently identify more vulnerable lines than established structural and electrical baselines.
Tianxin Zhou, Xiang Li, Haibing Lu
Department of Computer Science & Engineering, Santa Clara University, Santa Clara, USA · Dept. of Information Systems & Analytics, Santa Clara University, Santa Clara, USA
Solving the alternating current power flow equations in real time is essential for secure grid operation, yet classical Newton-Raphson solvers can be slow under stressed conditions. Existing graph neural networks for power flow are typically trained on a single system and often degrade on different systems. We present PowerModelsGAT-AI, a physics-informed graph attention network that predicts bus voltages and generator injections. The model uses bus-type-aware masking to handle different bus types and balances multiple loss terms, including a power-mismatch penalty, using learned weights. We evaluate the model on 14 benchmark systems (4 to 6,470 buses) and train a unified model on 13 of these under N-2 (two-branch outage) conditions, achieving an average normalized mean absolute error of 0.89% for voltage magnitudes and R^2 > 0.99 for voltage angles. We also show continual learning: when adapting a base model to a new 1,354-bus system, standard fine-tuning causes severe forgetting with error increases exceeding 1000% on base systems, while our experience replay and elastic weight consolidation strategy keeps error increases below 2% and in some cases improves base-system performance. Interpretability analysis shows that learned attention weights correlate with physical branch parameters (susceptance: r = 0.38; thermal limits: r = 0.22), and feature importance analysis supports that the model captures established power flow relationships.
Chidozie Ezeakunne, Jose E. Tabarez, Reeju Pokharel +1
Los Alamos National Laboratory, Los Alamos, NM, USA · Department of Physics, University of Central Florida, Orlando, FL 32816 USA