AC Power Flow Contingency Analysis Using a Single Deep Neural Network
Organizations: Elmore Family School of Electrical and Computer Engineering Purdue University, West Lafayette, IN 47906
Abstract
Contingency analysis using the AC power flow (AC-PF) model is a critical tool for accurate grid security assessment, but its computational burden increases with the number of operating scenarios and outage configurations to evaluate. Recent ML-based approaches typically require outage-specific training data, leading to offline training costs that scale with the number of contingencies. This work proposes a framework that reuses a single ML model trained solely on basecase AC-PF data to estimate post-contingency operating states under arbitrary single-line outages. The proposed approach formulates post-contingency state prediction as a fixed-point iteration. If the ML model is a deep neural network (DNN), we derive sufficient conditions that guarantee convergence and develop semidefinite programming (SDP) formulations to certify these conditions for a given DNN. Numerical tests on the IEEE 118-bus system demonstrate that the proposed SDP formulations are tight, that the certified conditions hold for all tested contingencies, and that the resulting method produces accurate post-contingency state estimates within only a few iterations.
Figures & tables
| Method | Total (s) | Per instance (ms) |
|---|---|---|
| Proposed method | 3.9369 | 0.2244 |
| NR flat | 9.5709 | 0.5407 |
| DC model | 0.0103 | 0.0006 |
| NR warm start | 8.7270 | 0.4931 |
| Jacobian factorization | 4.6770 | 0.2642 |
Power Systems
Power systems research studies the planning, operation, control, and protection of electrical grids and their integration with energy resources.
See all 231 papers