Demand from data centers and AI compute is growing rapidly and is increasing stress on the power grid. This load could be flexible through user adjustments and provide relief during energy scarcity events, yet today its flexibility is provided through utility call-ups or system-operator load shedding, and is invisible to the users whose workloads are being curtailed. In this work, we propose to quantify and couple the prices of compute and energy in a single optimization problem. The resulting compute price reflects the marginal cost of the binding constraints and decomposes into components indicating which grid, power, hardware, or service requirement causes a price surge. The economic interpretation updates the price with real-time conditions and gives users a signal for potential flexibility provision. The co-optimization ultimately connects compute and energy markets while providing a signal for relief of stress on both the grid and the compute resources.
Figures & tables
Compute price
Grid endogenous (OPF)
Network/latency
Operating modes (batch size)
SLO reserve (queueing)
Elastic demand
Rao et al. [ 10 ] ; Liu et al. [ 11 , 12 ]
–
–
✓
–
( ✓ )
–
Lindberg et al. [ 13 , 14 ]
–
✓
–
–
–
–
Lin et al. [ 15 ]
–
✓
–
–
–
–
Zhang et al. [ 16 , 17 ]
–
✓
–
–
–
✓
Gu and Qin [ 18 ]
–
✓
–
–
–
–
Ding et al. [ 21 ]
–
✓
–
–
–
–
TABLE I: Comparison with the related work. ✓: addressed; ( ✓ ): partially or as an extension; –: not addressed.
Component
Value
Grid energy
PUEeνref
Grid congestion
PUEe(νn−νref)
Site power
PUEeμP
GPU scarcity
aμG
SLO headroom
(ρ−1−1)a[μG+PUEπ0(νn+μP)]
TABLE II: Components of the compute price, before dividing by τ .
Conversation
Agentic
Offline
Trace for lengths
conv.
code
conv.
nkin/nkout (ratio)
16
114
16
Share of requests
50%
30%
20%
ITL target Lk (ms)
30
50
–
RTT budget Rk (ms)
50
100
–
Wait target Wk (s)
1
10
–
TABLE III: Request classes. Bids use ε=1 and NB=10 segments.
Event
Base
GPU failure
power limit
grid event
LMP at DC1 ($/MWh)
56.6
55.3
55.9
2,413.3
DC1 power (MW)
21.8
7.66
10.0
12.1
Conversation price
0.007
0.400
0.316
0.270
Agentic price
0.005
0.235
0.229
0.197
Offline price
0.006
0.262
0.255
0.219
Conversation served (%)
100
90.6
96.9
100
TABLE IV: Results at the peak hour. Prices are for region 1 in $/M-tokens; served shares are fleet-wide.
Fig. 1: IEEE 30-bus system with the three data-center sites. Red lines are loaded at or above 80% at the peak hour without data centers.
Fig. 2: Demand bids (black) and residual supply (colored) for region 1 at the peak hour, per event. Intersections mark the cleared quantity and price.
Fig. 3: Compute prices in region 1 and the electricity LMP at the DC1 bus over the day. The shaded area is the event window.
Fig. 4: Components of the input- and output-token prices in region 1 at the peak hour, per event. Labels give the site serving most of each class.
Sep 8, 2026·Alexander Crosier, Kyle Onghai, Ronnie SircarPower Systems
Formerly Princeton University · ORFE Department, Princeton University · ORFE Department, Bendheim Center for Finance and Andlinger Center for Energy & the Environment, Princeton University