Multi-Library Feature Engineering and Statistically Validated Classification for Power Swing Detection and Stability Assessment

Authors: Pallav Kumar Bera, Samita Rani Pani, Ranjeeta Patel

Organizations: Western Kentucky University, KY, USA · KIIT DU, Odisha, India

Abstract

Faults occurring during power swings, and the evolution of a swing into an unstable condition, cause distance-relay maloperation and cascaded outages. This paper identifies faults, faults during power swings, and power swings, and distinguishes stable from unstable swings in a 9-bus WSCC system modeled in PSCAD/EMTDC. Three time-series feature libraries (tsfresh, TSFEL, and tsfeatures) are applied to the 3-phase relay voltages and currents, giving 3286 statistical, temporal, spectral, and fractal descriptors per event window. A two-step feature selection (Boruta all-relevant filtering followed by RFECV- and SHAP-guided minimal-optimal pruning) reduces the feature set to 18 compact, non-redundant features. 14 classifiers spanning linear, kernel/instance-based, probabilistic, neural, and tree-ensemble/boosting families are then benchmarked under repeated stratified cross-validation, with model differences assessed by a Friedman/Nemenyi omnibus-and-post-hoc test and a Nadeau--Bengio corrected paired t-test. Rotation Forest (ROF) identifies the three event types with 99.98% and SVM-RBF distinguishes stable from unstable swings with 97.97% balanced accuracy. The results show that automated, library-driven feature extraction combined with rigorous statistical model comparison achieves near-perfect discrimination while retaining feature-level interpretability through SHAP importance.

Figures & tables

Explore similar work

Aug 24, 2026

A Hybrid Two-Stage Machine Learning Pipeline for Fault Detection and Classification in Power Transmission Systems

Rapid and accurate fault detection in high-voltage transmission networks is essential for grid reliability and equipment protection. Transmission fault datasets are frequently imbalanced, and certain fault types produce electrical signatures that fall within the normal operating envelope, causing single-model classifiers to fail on safety-critical cases. This paper proposes a hybrid two-stage machine learning pipeline that decouples detection from classification. Stage 1 combines an Isolation Forest anomaly detector with an optional supervised binary detector through an OR-fusion rule; the supervised branch is allocated automatically during training for any fault class the anomaly detector cannot resolve, and is omitted when no such class exists. Stage 2 applies a Random Forest multiclass classifier only to samples flagged by Stage 1. Feature engineering is expressed as a per-measurement-point operator mapping six raw channels to eighteen features, including zero-sequence symmetrical components derived from Fortescue's theorem, yielding 18L features for L measurement points. On the TLFaultDataset, the pipeline raises Line-fault end-to-end accuracy from 31.3% to 95.8%. On an independent single-point dataset, the same framework attains 97.25% end-to-end accuracy across all classes including normal operation, exceeding the TLFed federated benchmark of 94.84% without GPU or federated infrastructure, at 0.05 ms per sample on CPU. Ablation on both datasets shows zero-sequence features resolving the three-phase versus three-phase-to-ground ambiguity, raising the F1-score of that class pair from 0.39 to 0.997. The direction of the zero-sequence signature is found to be system-dependent, motivating a learned decision boundary in place of a fixed relay threshold.
Oct 31, 2026

Benchmarking Classical Machine Learning Models for Shading-Fault Detection in Rooftop Photovoltaic Systems Using Real Sensor Data

Most published comparisons of machine-learning classifiers for photovoltaic (PV) fault detection are validated on simulated faults. We compare seven classical and ensemble-tree classifiers on the Réunion dataset, a 4 kW domestic rooftop plant on which shading faults were physically staged and logged. Readings within a staged episode are near-duplicates, so every train/test split is grouped by episode. A 20,800-row subsample that retains all 17 fault episodes was evaluated with three repeats of five-fold group-aware nested cross-validation, with synthetic minority oversampling (SMOTE) applied inside the training folds. Random Forest and XGBoost gave the highest mean accuracy (0.838 and 0.831) and Matthews correlation coefficient (MCC; 0.526 and 0.522). After Holm correction across the 21 pairwise Wilcoxon tests, only Random Forest's accuracy advantage over k-nearest neighbours and the multi-layer perceptron remained significant. Logistic Regression and the Decision Tree (accuracy 0.820) could be separated neither from the ensembles nor from the weakest models. SMOTE lowered binary MCC for six of the seven classifiers. Errors were concentrated in whole episodes: the Random Forest almost entirely missed four of the 17 fault episodes, including one of two uniform-shading and two of five intermittent-shading episodes. A post-hoc diagnostic shows that the no-fault rows were sampled over a wider range of times of day and output levels than the fault rows. Clock time alone reaches an MCC of 0.44, and PV-side voltage alone 0.72. The reported scores therefore reflect operating-condition differences as well as shading signatures. We release the pipeline and the diagnostics, and identify matched no-fault sampling as the step needed before the classifier ranking can be generalised.
Nov 13, 2026

Protection-Oriented Assessment of Machine Learning-Based Fault Detection in Power Systems

Machine learning (ML)-based fault detectors are increasingly proposed for power system protection, yet aggregate metrics can obscure the consequences of false and missed trips. We present a protection-oriented assessment of three ML detectors and a sequence-current reference on PROTECT-90, comprising 9,022 simulated fault episodes on a 90 kV double-circuit line. The assessment combines five window conditions, causal window-end labelling, episode-grouped cross-validation, and operating-point selection under a fixed security budget. It reports security, dependability, detection timing, decision margins, and episode-level nuisance assertions. Gradient-boosted trees, a convolutional neural network, and logistic regression achieve AUC-ROC values above 0.999, yet at a security budget of 10−310^{-3} their developed-fault missed-trip rates range from 0.007% to 1.99%. Post-clearing false-trip rates of approximately 0.12-0.16% per window coexist with nuisance assertions in 11.3-19.1% of episodes. Among the analysed physical descriptors, missed trips are most consistently associated with higher fault resistance within the sampled range. An analytical current proxy suggests a fault-current gradient only partly reproduced by waveform-derived current (rank correlation 0.62). No single topology state or faulted phase consistently dominates within the sampled domain. Because PROTECT-90 contains fault episodes only, security is assessed on pre-fault and post-clearing windows rather than independent non-fault disturbances.