LAaDT-DSS: decision support for non-experts on rooftop PV, incentive and grid simulations under Turkish tariff rules
Organizations: Department of Information Systems Engineering, Sakarya University, Sakarya, Türkiye
Abstract
Rooftop photovoltaics raise three questions: should a household invest, which incentive costs the state least, and does the feeder stay within limits? Those who ask are rarely modellers. We present LAaDT-DSS, decision-support software that answers all three under Turkish tariff rules from one simulation core. Non-experts reach it by clicking a house on a 3D map or by asking in plain words; a language model is asked to call the simulation tools, not to compute. Each entry of its 125-entry parameter registry is marked as sourced or estimated. Case studies test the system. Its PV yield lies within 3.6% of two independent tools at equal losses. Across 2,048 draws of its estimated inputs, the answer for PV alone held in all but one; with a battery, it changed in 31-41% of the draws. Four scripted chat scenarios ran end to end; no user study was run.
Figures & tables
| Tool | Building NPV, PV and battery | Incentives by state cost | Feeder voltage and loading | Engine checked against | Input uncertainty | Licence |
|---|---|---|---|---|---|---|
| SAM | yes | not found | not found | measured data, other tools | parametric and stochastic runs | BSD-3 |
| REopt | yes, cost-optimal size | not found | no | not found | scenario batches | Apache/BSD |
| HOMER | yes | not found | no | not found | sensitivity grids over two inputs | commercial |
| dGen | partly, for sampled agents | partly: adoption, not cost | not found | calibrated to installation counts | Monte Carlo over agents | BSD-3 |
| pylovo | not found | not found | yes | reference grids, OpenDSS | one input at a time | MIT |
| URBANopt | yes, cost-optimal size (REopt) | not found | yes; feeders drawn or generated | not found | scenario runs | BSD-3 |
| Component | Reference | Case | Result |
|---|---|---|---|
| Load flow | OpenDSS ( dugan2011 ), same networks, positive sequence | Three synthetic feeders (116–260 buses), evening and noon | Voltage within 0.00021 pu; loading within 0.08 percentage points |
| Load flow | OpenDSS | SimBench 1-LV-rural1 (15 buses) | Voltage within 0.00013 pu; loading within 0.005 percentage points |
| Cash flow | SAM, same first-year inputs | PV only, 5 kWp, 4,000 kWh/yr, Sakarya and Ankara, hourly netting, low-tier export price (Section 6.1) | First-year savings +1.3 and +0.3 %; NPV −9.8 and −11.5 % |
AI-Assisted Decision Making
AI-assisted decision making studies how computational systems can inform human choices while accounting for context, uncertainty, and consequences.
See all 166 papers