cs.LGMay 23, 2025

Unsupervised Clustering for Fault Analysis in High-Voltage Power Systems Using Voltage and Current Signals

Authors: Julian OelhafGeorg KordowichAndreas MaierJohann JägerSiming Bayer

Abstract

The widespread use of sensors in modern power grids has led to the accumulation of large amounts of voltage and current waveform data, especially during fault events. However, the lack of labeled datasets poses a significant challenge for fault classification and analysis. This paper explores the application of unsupervised clustering techniques for fault diagnosis in high-voltage power systems. A dataset provided by the Réseau de Transport d'Électricité (RTE) is analyzed, with frequency domain features extracted using the Fast Fourier Transform (FFT). The K-Means algorithm is then applied to identify underlying patterns in the data, enabling automated fault categorization without the need for labeled training samples. The resulting clusters are evaluated in collaboration with power system experts to assess their alignment with real-world fault characteristics. The results demonstrate the potential of unsupervised learning for scalable and data-driven fault analysis by structuring large unlabeled waveform datasets and supporting targeted expert review.

Explore similar work

Jun 14, 2026eess.SP

Early Anomaly-Onset Detection based on Wigner--Ville Distribution Slice Spectra: A Transmission-Grid Test Case

Operational disturbance monitoring in power networks requires decisions to be made from waveform windows as they arrive, rather than from completed records after the event. This study evaluates full-vector Wigner--Ville Distribution Slice (WVDS) spectra for sequential anomaly-onset detection in high-voltage grid-voltage waveforms. The approach keeps the bilinear midpoint interaction structure of the Wigner--Ville distribution and represents each 128-sample voltage window by a 128-dimensional slice spectrum, avoiding manually selected fault-frequency markers. WVDS is used with a baseline-normalized deviation (BND) score and is compared against the BND of Fast Fourier Transform (FFT-BND), raw-window autoencoders, FFT autoencoders, and WVDS autoencoders under the same thresholding and three-window persistence rule. A synthetic autoencoder--clustering teacher is used to select RTE fault records that start from an initially normal region and then transition to anomalous behavior. On the filtered test set, FFT-BND achieves the highest sensitivity, whereas WVDS-BND provides the lowest false-alarm operating point, reducing record-level pre-onset false alarms to 0.69%. The autoencoder comparison follows the same selectivity pattern: WVDS reconstruction decreases false alarms relative to FFT reconstruction but misses more examples. The results indicate that preserved WVD cross-term information can form a selective representation for online grid-waveform anomaly monitoring when false alarms are costly.
Eduardo Jr Piedad, Eduardo Prieto-Araujo, Oriol Gomis-Bellmunt
Apr 22, 2026cs.LG

Domain-Aware Hierarchical Contrastive Learning for Semi-Supervised Generalization Fault Diagnosis

Fault diagnosis under unseen operating conditions remains highly challenging when labeled data are scarce. Semi-supervised domain generalization fault diagnosis (SSDGFD) provides a practical solution by jointly exploiting labeled and unlabeled source domains. However, existing methods still suffer from two coupled limitations. First, pseudo-labels for unlabeled domains are typically generated primarily from knowledge learned on the labeled source domain, which neglects domain-specific geometric discrepancies and thus induces systematic cross-domain pseudo-label bias. Second, unlabeled samples are commonly handled with a hard accept-or-discard strategy, where rigid thresholding causes imbalanced sample utilization across domains, while hard-label assignment for uncertain samples can easily introduce additional noise. To address these issues, we propose a unified framework termed domain-aware hierarchical contrastive learning (DAHCL) for SSDGFD. Specifically, DAHCL introduces a domain-aware learning (DAL) module to explicitly capture source-domain geometric characteristics and calibrate pseudo-label predictions across heterogeneous source domains, thereby mitigating cross-domain bias in pseudo-label generation. In addition, DAHCL develops a hierarchical contrastive learning (HCL) module that combines dynamic confidence stratification with fuzzy contrastive supervision, enabling uncertain samples to contribute to representation learning without relying on unreliable hard labels. In this way, DAHCL jointly improves the quality of supervision and the utilization of unlabeled samples. Furthermore, to better reflect practical industrial scenarios, we incorporate engineering noise into the SSDGFD evaluation protocol. Extensive experiments on three benchmark datasets demonstrate that...
Junyu Ren, Wensheng Gan, Philip S Yu
Aug 6, 2026cs.LG

Spectral Aliasing Pretext: A novel task for Self-Supervised fault diagnosis in rotating machinery

Deep learning is a new way for machinery fault diagnosis but requires extensive labeled data, a scarce resource in industrial settings. We propose Spectral Aliasing Pretext (SAP), a self-supervised learning method that pretrains models on unlabeled vibration data by exploiting spectral aliasing. We deliberately undersample signals to create folded spectrum, then train a Transformer to reconstruct the original unfolded spectrum. This pretext task forces the model to learn frequency-domain invariants characteristic of mechanical faults, without potentially destructive augmentations. Experiments on the CWRU dataset show that SAP learns stable and highly discriminative representations. In a linear probing setting, SAP quickly achieves very high classification performance with only a small fraction of labeled data and low variance. In contrast, full fine-tuning, including fully supervised training, does not lead to more stable or better results. Overall, these findings suggest that SAP combined with linear probing can be more effective and reliable than fully supervised training for fault diagnosis with limited labeled data.
Victor Gialis, Maxime Metz, David Esteve +1