Organizations: IFP Energies Nouvelles, Rond-point de l’´echangeur de Solaize, BP 3, 69360 Solaize, France · Universit´e de Lorraine, CNRS, CRAN, F-54000 Nancy, France
Classical Fault Detection and Diagnosis (FDD) methods, including many data-driven approaches, assume a static normal operating space and interpret deviations from a fixed reference as fault indicators. When Operating Conditions (OCs) vary over time, this assumption breaks down: legitimate transitions trigger false alarms while moderate faults go undetected. We propose a spatiotemporal Graph Neural Network (GNN) framework that decomposes the normal operating space into OC-specific subspaces linked by transition functions, with a dual learning objective combining reconstruction loss and a Deep SVDD one-class term. It learns adjacency matrices through Graph Attention Networks (GATs) and integrates spatial modelling with temporal encoding to represent process dynamics under evolving OCs. This paper evaluates the framework's foundational components (fault detection, GATv2 spatial graph learning and temporal encoding) on the Tennessee Eastman Process (TEP) benchmark, training only on fault-free data. The architecture achieves competitive detection from reconstruction error alone, with similarity-based feature selection improving both accuracy and graph structure diversity. We then evaluate the physical interpretability of the learned attention matrices against 22 ground-truth sensor pairs derived from the TEP control structure and process topology. GATv2 attention fails to recover all known physical pairs across multiple hyperparameter configurations, suggesting a structural limitation of reconstruction-driven attention rather than a tuning issue. This challenges a common assumption in GNN-based FDD: that learned attention weights provide a basis for fault diagnosis and root-cause analysis. The architecture detects faults effectively, but the learned graph does not encode the physical topology needed for interpretable diagnosis, motivating physics-informed graph construction.
Figures & tables
Figure 1: Single-threshold detection (left) versus OC-aware detection (right).
Figure 2: Dual-loss framework. Left: the spatiotemporal Graph Autoencoder (GAE) for reconstruction. Right: a Deep SVDD-inspired one-class loss maps normal data to a compact hypersphere in latent space.
Figure 3: Architecture of the spatiotemporal graph attention autoencoder. The 1-D ConvLayer provides local temporal smoothing. Feature attention (GATv2) learns inter-sensor relationships; temporal attention models timestep dependencies. Both outputs are concatenated and encoded by a GRU. A linear decoder reconstructs x^t=T ; reconstruction error serves as the anomaly score.
Exp.
feat_embed
window
dropout
A
16
50
0.2
B
32
50
0.2
C
64
25
0.2
D
32
25
0.3
E
64
50
0.4
Table 1: Hyperparameter configurations of experiments ( kernel =7).
Exp.
f_embed
w
drop
ROC-AUC
PR-AUC
A
16
50
0.2
0.772
0.803
B
32
50
0.2
0.771
0.803
C
64
25
0.2
0.752
0.784
D
32
25
0.3
0.754
0.786
E
64
50
0.4
0.771
0.802
Table 2: Mean detection performance across 20 TEP faults ( f_embed is feature embedding, w is the window size and drop is the dropout rate).
F.
Type
ROC
PR
1
Step
0.700
0.769
2
Step
0.640
0.696
3 †
Step
0.500
0.500
4
Step
0.515
0.545
5
Step
0.633
0.702
6
Step
0.912
0.938
Table 3: Per-fault detection performance for Experiment A. Faults marked † are widely regarded as undetectable in the TEP literature and are routinely excluded from comparison studies.
Method
Faults
Reported metric
TGGL jia2023
20/20
FDR ≈0.83
CNN-GAT liu2024
20/20
FDR ≈0.85
This work (Exp. A)
20/20
ROC-AUC 0.77 PR-AUC 0.80
TEP F1 is taken from a re-implementation reported by jia2023 .
FDR = Fault Detection Rate at fixed false alarm rate.
Table 4: Reported TEP detection performance for representative methods. Protocols differ across studies; values are reproduced as published.
k
GAT hits
GAT rate
Pearson hits
Pearson rate
10
0
0.0%
4
40.0%
20
1
5.0%
4
20.0%
30
2
6.7%
6
20.0%
50
2
4.0%
7
14.0%
Table 5: Hit-Rate@ k : fraction of top- k pairs matching physical ground truth (22 pairs total). GAT = learned attention; Pearson = ∣ρij∣ baseline.
Exp.
Config.
Hits@30
Rate
A
16 / 50 / 0.2
1
3.3%
B
32 / 50 / 0.2
1
3.3%
C
64 / 25 / 0.2
0
0.0%
D
32 / 25 / 0.3
0
0.0%
E
64 / 50 / 0.4
1
3.3%
Table 6: Hit-Rate@30 across hyperparameter configurations.
Var.
Name
Unit
xmeas_1
A Feed (stream 1)
kscmh
xmeas_2
D Feed (stream 2)
kg/hr
xmeas_3
E Feed (stream 3)
kscmh
xmeas_4
A and C Feed (stream 4)
kscmh
xmeas_5
Recycle Flow (stream 8)
kscmh
xmeas_6
Reactor Feed Rate (stream 6)
kscmh
Table 7: TEP continuous process measurements (Vertical Layout).
Variables
Description
Sampling (h)
Dead Time (h)
xmeas_23 to xmeas_29
Reactor Feed Analysis (Stream 6)
0.1
0.1
xmeas_30 to xmeas_37
Purge Gas Analysis (Stream 9)
0.1
0.1
xmeas_38 to xmeas_41
Product Analysis (Stream 11)
0.25
0.25
Table 8: TEP composition analyser variables (Unit is in %mol).
Var.
Name
Unit
Var.
Name
Unit
xmv_1
D Feed Flow (stream 2)
kg/hr
xmv_7
Sep Pot Liquid Flow (stream 10)
m 3 /hr
xmv_2
E Feed Flow (stream 3)
kg/hr
xmv_8
Stripper Product Flow (stream 11)
m 3 /hr
xmv_3
A Feed Flow (stream 1)
kscmh
xmv_9
Stripper Steam Valve
%
xmv_4
A and C Feed Flow (stream 4)
kscmh
xmv_10
Reactor Cooling Water Flow
m 3 /hr
xmv_5
Compressor Recycle Valve
%
xmv_11
Condenser Cooling Water Flow
m 3 /hr
xmv_6
Purge Valve (stream 9)
%
Table 9: TEP manipulated variables.
F.
Description
Type
F.
Description
Type
1
A/C feed ratio, B comp. (Str. 4)
Step
10
C feed temp. (Str. 4)
Random
2
B comp., A/C ratio (Str. 4)
Step
11
Reactor CW inlet temp.
Random
3
D feed temp. (Str. 2)
Step
12
Condenser CW inlet temp.
Random
4
Reactor CW inlet temp.
Step
13
Reaction kinetics
Slow Drift
5
Condenser CW inlet temp.
Step
14
Reactor CW valve
Sticking
6
A feed loss (Str. 1)
Step
15
Condenser CW valve
Sticking
Table 10: TEP fault descriptions and types.
#
Sensor A
Sensor B
Description
Category 1 — Control loops (11 pairs)
1
xmeas_7
xmv_4
Reactor pressure / A+C feed flow
2
xmeas_7
xmv_6
Reactor pressure / purge valve
3
xmeas_8
xmv_10
Reactor level / reactor CW flow
4
xmeas_9
xmv_7
Reactor temperature / separator liquid flow
5
xmeas_10
xmv_1
Purge rate / D feed flow
Table 11: The 22 ground-truth physical sensor pairs used for Hit-Rate@ k evaluation, grouped by source of process knowledge.
Figure 4: GATv2 feature-attention matrix learned under normal operating conditions (35 features, Experiment A). Bright vertical stripes indicate hub columns — sensors that receive high attention from many source nodes.
Figure 5: GATv2 feature-attention matrices computed on each of the 20 TEP fault scenarios (Faults 1–20, left-to-right, top-to-bottom). Each panel shares the same axes, ordering, and colour scale as Figure 4 : rows and columns index the 35 selected sensors.
Fault detection identifies abnormal behavior in machines, sensors, infrastructure, software, and autonomous systems before it causes harm or disruption.