Self-Supervised Learning for Soft-Constrained AC-OPF in Multiphase Distribution Systems
Organizations: Massachusetts Institute of Technology, Cambridge, MA, USA. · GE Vernova Advanced Research Center, Niskayuna, NY, USA.
Abstract
This paper presents a self-supervised learning framework for fast, soft-constrained AC optimal power flow (OPF) in unbalanced multiphase distribution systems. The soft AC-OPF objective balances operating cost, renewable energy curtailment, and penalties for violating operating limits. A neural network predicts distributed energy resource (DER) setpoints conditioned on operating conditions, switch configurations, and objective weights. The predicted setpoints are then processed through a DER projection and differentiable AC power flow to enforce device limits and network equalities. The framework is trained by directly minimizing the AC-OPF objective, without optimal-solution labels. Experiments on 123-, 240-, and 906-bus systems yield mean objective gaps of 0.32%, 0.92%, and 0.56%, respectively, relative to IPOPT, across wide operating ranges. Across these systems and the evaluated high-load/low-generation and low-load/high-generation scenarios, the largest mean gap is 1.04%, with mean speedups of 58-5272 times relative to IPOPT.
Figures & tables
| Grid | Method | wide | high-load/low-DER | low-load/high-DER |
| 123 bus | Ours | 0.32 ±0.03 ( 408) | 0.01 ±0.00 ( 626) | 0.13 ±0.01 ( 418) |
| Direct Prediction | 300.40 ±68.26 ( 333) | 47.62 ±60.49 ( 515) | 448.44 ±238.39 ( 339) | |
| 240 bus | Ours | 0.92 ±0.01 ( 79) | 0.92 ±0.03 ( 59) | 1.04 ±0.01 ( 67) |
| Direct Prediction | 74.14 ±4.29 ( 76) | 8.23 ±0.47 ( 58) | 350.10 ±19.69 ( 65) | |
| 906 bus | Ours | 0.56 ±0.09 ( 5272) | 0.04 ±0.01 ( 4466) | 0.03 ±0.00 ( 3907) |
| Direct Prediction | 218.04 ±59.74 ( 4521) | 137.28 ±81.42 ( 3863) | 82.59 ±17.39 ( 3455) |
Optimal Power Flow
Optimal Power Flow (OPF) finds low-cost power-system operating plans that satisfy network, voltage, and equipment constraints.