Online Identification Can Replace a Floor-Plan Prior on Unseen Buildings
Authors: Elias T. -H. Shieh, Chun Fu
Organizations: Siebel School of Computing and Data Science, University of Illinois Urbana-Champaign · Department of Bioenvironmental Systems Engineering, National Taiwan University
The Smart Buildings Challenge asks for one HVAC control policy that runs office buildings and weather it has never seen, from the building's metadata and sensor streams alone. Our controller sees no data from the target building before it runs and is not tuned per building; its few global constants were set on development scenarios. Each zone has a first-order grey-box model that starts from coefficients computed from the floor plan and is updated online by recursive least squares, and a planner and a closed-form mapping turn the models into plant commands. On two sets of buildings and weather that we generated, a validation set and a stress set with real-year weather, it scores 0.145 and 0.159 times the starter kit's PID baseline, and 0.095 times on a holdout built after all versions were fixed and scored once. It improves on every building, also against our two implementations of ASHRAE Guideline 36: per set it scores 0.60 to 0.71 times a basic version and 0.83 to 0.96 times one partly tuned on the public leaderboard, which wins one of 54 scenarios; with a 5 °C frost target for empty zones on both, the margin over the tuned version shrinks to 1.4% on the stress set, where one of six buildings is 0.2% worse. In an ablation on a reduced-order model, removing both the floor-plan prior and online identification costs 28%, 20% and 42% on the validation, stress and holdout sets, far more than the two effects combined: either source of building-specific information recovers most of what is lost without both. On one office floor in a second simulator, BOPTEST, this does not carry over: with identification on, the two priors give similar results, but the floor-plan prior alone, with constants fitted on the competition's simulator, is the least stable arm. These simulation results motivate testing floor-plan-initialised adaptive control in buildings that have drawings but no operating data.
Figures & tables
Figure 1: The controller, drawn schematically; nothing is fitted to the building in advance. Each zone’s model starts from the floor-plan prior (step 1, with the room’s cells at the exterior dark; § 4.2 ) and is corrected by recursive least squares (step 2, § 4.1 ); the planner gives each zone the interval of heat that reaches the comfort band (step 3, § 4.3 ); a closed-form mapping turns it into device commands (step 4, § 4.4 ).
Figure 2: The floor-plan prior as the controller reads it: the zone map of validation-set building_10002 (two floors), each room coloured by its starting heat-gain coefficient θ2,i0 of ( 4 ) with s=1 (cold weather; rooms of at most 50 cells keep θg ). RLS then corrects these values.
Figure 3: Every scenario improves on the PID baseline and a basic Guideline 36 baseline (G36; the tuned G36-t is closer, Table 1 ), including a holdout scored once after all versions were fixed (formal scores, stock simulator; ratio to PID, log scale; lower is better). Each panel is one set of six unseen buildings with three weather scenarios each: (a) official weather strips and (b) the stress set, real-year weather with a hot and a cold month per building (§ 5 ); (c) the holdout (Appendix B.24 ). One mark per scenario: navy dot ours, orange triangle G36; dashed lines and the values at their right: each controller’s ratio over all 18. (a) and (b) informed which versions we kept; (c) did not.
validation set
stress set
holdout
policy
stock
boilerfix
stock
stock
public
PID baseline (starter kit)
0.034134
0.036033
0.10132
0.042057
0.06404
Guideline 36, basic (G36)
0.007430
0.007431
0.022678
0.006700
0.01385
Guideline 36, tuned (G36-t)
0.005513
0.005493
0.016779
0.004805
0.01044 †
with 5 °C deep-cold floor
0.005548
–
0.017160
0.004804
–
first model-based (v0c)
0.005674
0.005670
0.017416
–
0.01095
Table 1: Mean ∣rˉ∣ over scenarios (lower is better): formal on the official simulator (stock) and its billing-corrected copy (boilerfix); Kaggle public leaderboard (other scenarios; † partly tuned on it). –: not run; frost target: a soft 5 °C planning target for unoccupied zones (§ 7 ); deep-cold floor: G36-t’s unoccupied floor in deep cold raised from −3 to 5 °C (Appendix B.25 ).
Figure 4: Ablation of the model layer on the three sets (reduced model, ratio to the submitted policy; >1 is worse). Filled marker and number: ratio over all 18 scenarios; bar: its range when one building is left out (hidden where shorter than the marker; values in Appendix B.9 ); circles: the six buildings (overlapping where nearly equal). Open diamond: the product of the RLS-frozen and global-prior rows, the cost without interaction (1.069, 1.099 and 1.048).
Appendix figures & tables8 assets
Supplementary material from the paper’s appendix.
Appendix
Figure 5: (a) v1o (v1n with the CMA-ES constants) against v1n (formal gates): bar, all 18 scenarios; circles, buildings; dots, scenarios; diamonds, building_14006 and its scenarios. On val18p every scenario improves; on hard18x the aggregate is 4.1% worse, and building_14006 accounts for all of the net loss (101%), its Duluth January scenario alone for 103% (the shares exceed 100% because the other five buildings net a small gain: three improve, 14014 is 5.7% and 14000 0.6% worse). (b) Ratio of the public-leaderboard scores of consecutive submitted versions against the ratio of their local scores (val18p and hard18x pooled), with both ratios printed at the right; the largest log error is 0.0096.
policy
val18p stock
val18p boilerfix
hard18x stock
public
v1r (analysed in the paper)
0.004956
0.004956
0.016088
0.00996
v1s
0.004945
0.004945
0.015959
0.00991
v1t
0.004937
0.004937
0.015889
0.00984
v1u
0.004889
0.004889
0.015825
0.00978
v1w
0.004859
0.004836
0.015692
–
v1x
0.004833
0.004811
0.015593
0.00964
Appendix
Table 2: Later versions (formal gates; public: Kaggle public leaderboard). v1w was not submitted on its own.
Figure 6: When each ablated part loses. For each arm, the cumulative share of its 30-day excess loss over v1r (summed over the 18 scenarios of each set, reduced model), by day of the episode; the dashed diagonal is an even spread, the dotted line marks day 7, and the numbers are the shares lost by then; markers sit on their lines at weekly intervals; a share can pass 100% for a few days where the arm does better than v1r. Light bands on val18p: the four days on which v1r has almost no loss (unoccupied). The prior’s loss is front-loaded and returns after the first two unoccupied days; identification’s loss accrues over the weeks.
quantity
v1r
PID baseline
score change, billing-corrected simulator
0.0%
+5.6%
return-air heat to zones / boiler heat
+0.19% (36 runs)
+2.85% , +2.83% (2 runs)
coldest scenario, no frost floor
zone-steps below 5 °C / below 0 °C
27% / 19%
0.09% / 0%
coldest zone; coldest zone while occupied
−30.3 / 9.8 °C
2.2 / 7.1 °C
boiler heat
149 MWh
396 MWh
Appendix
Table 3: What the score does not see. Billing: formal gate on val18p; all other rows reduced model (ROM). The coldest scenario is hard18x building_14008 in Fairbanks, January 2022; the frost rows pool the six cold hard18x scenarios.
Figure 7: The coldest stress-set scenario (14008, Fairbanks, Jan. 2022; ROM): coldest-zone temperature per controller. (a) Days 1–4, from a Saturday; (b) daily minimum (markers). Dotted: 5 °C.
Figure 8: The building of Figure 7 at the coldest moment of v1r’s episode, Monday 3 January 2022, 04:40, before the morning preheat: every room of its four floors coloured by its air temperature (reduced model). Rows: (a) the PID baseline, (b) v1r (the submitted policy, “our policy” in Figure 7 ), (c) v1r with the 5 °C frost target. Nobody is in the building at this hour, so none of the three is charged any comfort regret; only the energy and carbon of the heat they use count.
heating
cooling
arm
peak
typical
peak
typical
thermal discomfort
full (floor-plan prior + RLS)
2.81
0.55
7.35
0.87
RLS frozen
2.27
1.35
7.97
1.17
global prior
3.68
0.63
7.70
0.96
both removed
1.68
0.55
6.38
0.70
Appendix
Table 4: BOPTEST indicators per arm and scenario (two-week test periods; lower is better). Thermal discomfort in K h per zone, energy in kWh m -2 , CO 2 discomfort in ppm h per zone. Cost and emissions are proportional to energy here (all-electric plant, constant price) and are not shown. Baseline: the case’s own controller. One case, so the four scenarios are not independent buildings.
building
size
rooms
AHUs
weather strips
val18p (287 rooms)
10001
401 × 193 × 2
33
5
atlanta_7, denver_4, fairbanks_3
10002
409 × 214 × 2
29
7
minneapolis_6, phoenix_7, singapore_5
10004
433 × 266 × 2
47
6
atlanta_4, denver_1, fairbanks_6
10005
425 × 196 × 3
59
6
minneapolis_4, phoenix_2, singapore_2
10006
370 × 192 × 2
24
3
atlanta_7, denver_4, fairbanks_3
Appendix
Table 5: Buildings and weather strips of the validation and stress sets: size is width × height in floor-plan cells × storeys; rooms and AHUs as generated (the scenarios of one building share them).
Heating, ventilation, and air conditioning control optimizes building energy use while maintaining thermal comfort, indoor air quality, and equipment safety.