cs.LGJul 9, 2026

A Machine Learning Surrogate for Component Criticality Ranking in Interdependent Power-Communication Networks

Authors: Sohini RoyXheni Hylviu

Abstract

Cyber-physical power systems are vulnerable to cascading failures caused by tight interdependencies between power and communication infrastructures. Evaluating these failures over large N-k contingency sets with a high-fidelity simulator is computationally prohibitive for resilience planning. Using the previously published Modified Implicative Interdependency Model (MIIM) as the ground-truth cascade simulator, this paper develops a machine-learning surrogate that predicts contingency severity from leakage-free structural features and derives a component-criticality ranking for prioritized hardening analysis. On the IEEE 118-bus system, the Gradient Boosting surrogate achieves Spearman correlations of 0.849 for per-contingency severity prediction and 0.853 for per-component criticality ranking, while remaining stable across three independently sampled datasets. MIIM-derived component criticality itself reproduces only to a Spearman of approximately 0.85 under the present sampling pipeline, and the surrogate operates at this empirical ceiling to within sampling variation. Topological centrality measures on the full interdependent network provide meaningful baselines (Spearman 0.60-0.69), and feature ablation shows that the surrogate's advantage is driven primarily by inter-layer dependency information. These results support a two-stage workflow in which the surrogate rapidly ranks candidate components and MIIM is reserved for selective verification.

Explore similar work

Nov 28, 2022cs.LG

A Bayesian Approach for the Network Reconstruction of Interdependent Critical Infrastructure Systems from Cascading Failures

Analyzing the behavior of complex interdependent networks requires complete information about the network topology and the interdependent links across networks. For many applications such as critical infrastructure systems, understanding network interdependencies is crucial to anticipate cascading failures and plan for disruptions. However, data on the topology of individual networks are often publicly unavailable due to privacy and security concerns. Additionally, interdependent links are often only revealed in the aftermath of a disruption as a result of cascading failures. We propose a scalable nonparametric Bayesian approach to reconstruct the topology of interdependent infrastructure networks from observations of cascading failures. Metropolis-Hastings algorithm coupled with the infrastructure-dependent proposal are employed to increase the efficiency of sampling possible graphs. Results of reconstructing a synthetic system of interdependent infrastructure networks demonstrate that the proposed approach outperforms existing methods in both accuracy and computational time. We further apply this approach to reconstruct the topology of one synthetic and two real-world systems of interdependent infrastructure networks, including gas-power-water networks in Shelby County, TN, USA, and an interdependent system of power-water networks in Italy, to demonstrate the general applicability of the approach.
MirSaleh Bahavarnia, Hiba Baroud, Yu Wang +1
May 7, 2026cs.LG

Inductive Power Grid Cascading Failure Analysis with GRU-Gated Graph Attention

Identifying vulnerable transmission lines in power grids before a cascading failure occurs is challenging: existing methods can learn inter-line failure correlations from cascade data, but they are trained and evaluated on a single grid, and transferring the learned knowledge to an unseen grid remains an open problem. We address this by training a single Gated Recurrent Unit (GRU)-gated Graph Attention Network on combined cascading failure data from limited training grids and applying it directly to any unseen grid without retraining. A GRU gate controls what information each node retains or discards at each cascade iteration. Empirical evaluation shows that the model transfers zero-shot to multiple new grids spanning inter-time and inter-domain settings. Using information extracted from the trained model, we consistently identify more vulnerable lines than established structural and electrical baselines.
Tianxin Zhou, Xiang Li, Haibing Lu
Sep 7, 2026cs.AI

Data-Optimized Contingency Screening: A Machine Learning Approach to Power System Security

Ensuring the security of the power system is essential for stability and reliability, especially in the event of disruption. Effective classification of contingency in power systems enables proactive decision-making and mitigates large-scale breakdowns and failures. This study explores the use of machine learning algorithms to classify security levels of contingencies in power systems into safe, moderate or severe classes. For this approach, Newton-Raphson load flow method extracts system data from contingency scenarios, using Overall Performance Index (OPI) as safety measure. For data pre-processing, Synthetic Minority Over-Sampling Technique (SMOTE) and Principal Component Analysis (PCA) is used to address class imbalance and reduce dimensionality, respectively. K-Nearest Neighbours (KNN), Random Forest (RF) and Support Vector Machines (SVM) is trained and evaluated on datasets generated through N-k contingency scenarios for k equal 1, 2, and 3 on IEEE-14 and IEEE-30 bus systems using four hybrid pre-processing configurations: normalized, SMOTE-balanced, PCA-transformed, and a combined SMOTE PCA-transformed. Performance is assessed by precision, recall and F1 score, with priority given to the severe contingency classes. The RF achieved the highest F1 scores of 0.97 in IEEE-30 and 0.86 in IEEE-14, SVM benefits significantly from PCA and improves the accuracy of the classification, while KNN is best suited for SMOTE and PCA conversion. The findings show that PCA contributes more than SMOTE to the overall performance of the model. However, SMOTE improves recall but can introduce false positives and is therefore a compromise of accuracy. This study highlights machine learning as a scalable and powerful alternative to traditional contingency analysis, which improves the assessment of security in real time.
Joshua Salako, Folajimi Osikomaiya, Olakorede Olamiju