Distributed Volt--VAR control relies on voltage measurements and is therefore vulnerable to false-data injection. Neighbor corroboration can distinguish an isolated corrupted measurement from a physical disturbance, but coordinated agents can falsely corroborate one another. This paper proposes DynaTrust-VVC, a cyber-resilient multi-agent Volt--VAR framework that assigns each incoming neighbor message a directional trust value based on the consistency between its reported voltage increment and a sensitivity-based prediction from active- and reactive-power changes. Trust falls immediately after a physics mismatch and recovers gradually after sustained consistency. DynaTrust-VVC further uses a physics-adaptive evidence threshold and counterfactual safe-voltage recovery-based mitigation. The proposed method was validated using a nonlinear IEEE 123-bus feeder with minute-resolution residential profiles and 27 matched replicates. DynaTrust-VVC identifies a coordinated three-bus attack one minute after onset in all 27 matched replicates, whereas an otherwise identical configuration with fixed neighbor trust identifies none. The composite resilience index also increases from 0.227 to 0.315, with no statistically significant increase in the benign false-alarm rate.
Figures & tables
Fig. 1: Proposed DynaTrust-VVC framework for the multi-agent control pipeline, highlighting the dynamic physics-trust additions.
Symbol
Meaning
Value
Src.
AE
autoencoder 4−8−3−8−4 , ReLU
135 param.
D
θi0
AE reconstruction threshold
99th pct.
V
ηi
safe-state discrepancy scale
95th pct.
V
∣Ni∣
neighbors (strongest sensitivity)
3
D
SP,SQ
voltage sensitivities
OpenDSS FD
P
σphy
physics-residual scale ( 18 )
0.020 p.u.
D
TABLE I: Parameters and provenance. V = selected on validation days, P = physics-derived, D = fixed design constant.
The rapid proliferation of distributed energy resources (DERs) aggregated by virtual power plants (VPPs) elevates cybersecurity risk by expanding the attack surface. A coordinated cyberattack has the potential to disrupt distribution-system, bulk-system, and market operations. Existing cyberphysical defense strategies largely assume access to grid network models and operating conditions, which may not be available to third-party aggregators. This paper proposes a novel hybrid, perturbation-based cyber-physical defense for VPP-operated DERs that blends game-theoretic planning with model-free reinforcement learning (RL) under a Bayesian belief-update framework. Topology agnosticism is defined from the VPP information and implementation perspective: the VPP does not require access to the feeder topology, line parameters, switching configuration, or full system state. This work advances the state of the art through three contributions: (1) a multi-output Gaussian process with Hamiltonian Monte Carlo for discrete attacker-type inference, probability of detection, and confidence of detection for modeling the belief distribution; (2) moment-matched Gaussian propagation of posterior beliefs across episodes; and (3) an RL policy that adaptively integrates Stackelberg leader (VPP) actions with exploration. Furthermore, we establish equilibrium existence and derive an episode-level closed-loop utility bound connecting attacker-belief uncertainty with GT-RL action alignment. Evaluations on IEEE 13- and 123-Bus feeders with DER portfolios demonstrate effective detection under attacker-model uncertainty and evaluated feeder re-configuration conditions, while requiring no explicit feeder-topology knowledge. Overall, the results indicate that combining bi-level game-theoretic planning, nonparametric Bayesian inference, and adaptive RL is a promising direction for VPP cybersecurity.
Pooja Algikar, Stefano Fenu, Kumarsinh Jhala +1
the energy systems and infrastructure assessment division at Argonne National Laboratory
This work studies resilient output containment for heterogeneous linear multi-agent systems with actuator cyber-attacks over directed network topologies. The leaders generate bounded locally absolutely continuous trajectories; however, their dynamics, velocity bounds, and motion envelopes are undisclosed to the followers. The cyber-attack model includes state- and input-correlated, as well as bounded exogenous actuator false-data terms. A continuous two-layer adaptive control architecture is proposed. The first layer is a virtual-actuator reconfiguration layer that uses partial state measurements to compensate for actuator attacks in the local tracking-error dynamics. The second layer is a network interface that generates task-space commands via an adaptive interaction protocol. This protocol uses only neighbor-exchanged network-interface states whose dimensions match those of the plant output, and it does not require global graph knowledge for parameter tuning. For directed graphs, under a leader-rooted united spanning-tree condition, a nonsmooth Lyapunov analysis yields asymptotic containment at the command level. The physical outputs then converge to the leader convex hull up to a residual determined by the command-tracking local controllers. Simulation results using a network of quadrotors with damped suspended loads illustrate the performance of attack recovery and containment tracking.
Department of Electrical and Computer Engineering, Concordia University, Montreal, Canada. · Department of Electrical Engineering, Qatar University, Doha, Qatar.
As power systems advance toward net-zero targets, behind-the-meter renewables are driving rapid growth in distributed energy resources (DERs). Virtual power plants (VPPs) increasingly coordinate these resources to support power distribution network (PDN) operation, with EV charging stations (EVCSs) emerging as a key asset due to their strong impact on local voltages. However, in practice, VPPs must make operational decisions with only partial visibility of PDN states, relying on limited, aggregated information shared by the distribution system operator. This work proposes a safety-enhanced VPP framework for coordinating multiple EVCSs under such realistic information constraints to ensure voltage security while maintaining economic operation. We develop Transformer-assisted Lagrangian Multi-Agent Proximal Policy Optimization (TL-MAPPO), in which EVCS agents learn decentralized charging policies via centralized training with Lagrangian regularization to enforce voltage and demand-satisfaction constraints. A transformer-based embedding layer deployed on each EVCS agent captures temporal correlations among prices, loads, and charging demand to improve decision quality. Experiments on a realistic 33-bus PDN show that the proposed framework reduces voltage violations by approximately 45% and operational costs by approximately 10% compared to representative multi-agent DRL baselines, highlighting its potential for practical VPP deployment.
Chenghao Huang, Jiarong Fan, Weiqing Wang +1
Department of Data Science and AI, Faculty of IT, Monash University, Australia · Monash Energy Institute, Monash University, Australia