Grid-Oriented Probabilistic Load Forecasting for AI Data Centers

Authors: Qingyi Yao, Ding Lin, Tianqiao Zhao, Meng Yue, Jianhui Wang

Organizations: Southern Methodist University, Dallas, TX, USA · The University of Texas at Arlington, Arlington, TX, USA · Brookhaven National Laboratory, Upton, NY, USA

Abstract

Probabilistic load forecasts for AI data centers need to represent both uncertainty under changing workloads and temporal dependence to support grid operations. This paper develops an open, grid-oriented benchmark using measured GPU power from a 448-GPU AI cluster. Forecasts are evaluated through four stages: probabilistic prediction, online uncertainty calibration, temporal scenario generation, and horizon-wide reserve sizing. Following a change in cluster utilization, a quantile LightGBM forecast achieves only 63.4% coverage for a nominal 90% interval, while online regime-conditioned calibration increases coverage to 87.3%. Even with well-calibrated marginal forecasts, independent sampling produces unrealistic ramp distributions and excessive reserve procurement. Reconstructing temporal dependence from historical forecast errors reduces the discrepancy in ramp statistics and lowers realized reserve cost by 7.4-10.6% across three forecasting tasks. These findings show that marginal forecast quality alone is insufficient for operational decisions and motivate joint evaluation of calibration, temporal structure, and decision outcomes.

Figures & tables

Explore similar work

Apr 14, 2026

A Physics-Aware Framework for Short-Term GPU Power Forecasting of AI Data Centers

AI data centers experience rapid fluctuations in power demand due to the heterogeneity of computational tasks that they have to support. For example, the power profile of inference and training of large language models (LLMs) is quite distinct and big divergences can result in the instability of the underlying electricity grid. In this paper we propose, to the best of our knowledge, the first physics-informed DLinear time-series model that can accurately forecast power utilization of an AI data center 5-80 minutes (short-term forecasting) into the future. The physics, based on a multi-node lumped thermal resistance-capacitance (RC) network consistent with Newton's law of cooling, is captured using newly derived time-dependent ordinary differential equations (ODE) that separately models and interlinks power consumption with the GPU compute and memory utilization and temperature. The resulting model, that we refer to as PI-DLinear, trained and evaluated on a real AI data center dataset and is not only more accurate than the state-of-the-art (SOTA) models tested, but the forecast profile respects the underlying physics under power throttling and load transient events. Relative to the SOTA transformer-based and non-transformer-based models, improvements in forecasting accuracy (averaged across all look-back and prediction windows) range from 0.782%-39.08% for MSE, 0.993%-51.82% for MAE, and 0.370%-22.28% for RMSE.
Mar 9, 2026

Bayesian Transformer for Probabilistic Load Forecasting in Smart Grids

The reliable operation of modern power grids requires probabilistic load forecasts with well-calibrated uncertainty estimates. However, existing deep learning models produce overconfident point predictions that fail catastrophically under extreme weather distributional shifts. This study proposes a Bayesian Transformer (BT) framework that integrates three complementary uncertainty mechanisms into a PatchTST backbone: Monte Carlo Dropout for epistemic parameter uncertainty, variational feed-forward layers with log-uniform weight priors, and stochastic attention with learnable Gaussian noise perturbations on pre-softmax logits, representing, to the best of our knowledge, the first application of Bayesian attention to probabilistic load forecasting. A seven-level multi-quantile pinball-loss prediction head and post-training isotonic regression calibration produce sharp, near-nominally covered prediction intervals. Evaluation of five grid datasets (PJM, ERCOT, ENTSO-E Germany, France, and Great Britain) augmented with NOAA covariates across 24, 48, and 168-hour horizons demonstrates state-of-the-art performance. On the primary benchmark (PJM, H=24h), BT achieves a CRPS of 0.0289, improving 7.4% over Deep Ensembles and 29.9% over the deterministic LSTM, with 90.4% PICP at the 90% nominal level and the narrowest prediction intervals (4,960 MW) among all probabilistic baselines. During heat-wave and cold snap events, BT maintained 89.6% and 90.1% PICP respectively, versus 64.7% and 67.2% for the deterministic LSTM, confirming that Bayesian epistemic uncertainty naturally widens intervals for out-of-distribution inputs. Calibration remained stable across all horizons (89.8-90.4% PICP), while ablation confirmed that each component contributed a distinct value. The calibrated outputs directly support risk-based reserve sizing, stochastic unit commitment, and demand response activation.
Jun 23, 2026

Power-Flexible AI Data Centers: A New Paradigm for Grid-Responsive Compute

The rapid expansion of artificial intelligence (AI) infrastructure is driving unprecedented growth in electricity demand from data centers. Traditional power-system planning treats large computing facilities as inflexible peak loads, leading to costly infrastructure upgrades and long delays in grid interconnection. Recent work has shown that AI clusters can reduce electricity consumption during peak demand through software-based workload orchestration. This article explores how modern GPU-based AI data centers can operate as grid-interactive assets that respond dynamically to power system conditions. We describe an architecture integrating grid signals, workload scheduling, and power telemetry for fine-grained cluster power control. Experimental results from a real-world deployment on a 130 kW GPU cluster demonstrate multiple forms of flexibility, including rapid load reduction, sustained curtailment, and carbon-aware operation while preserving service levels for priority jobs. We further demonstrate performance-aware load shifting across geographically distributed clusters, enabling workloads to migrate toward regions with lower grid stress. Together, these capabilities transform AI infrastructure from static electricity consumers into flexible resources that support grid reliability, accelerate interconnection, and improve computing sustainability.